30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for the woodlands, tx


Map of The Woodlands TX
Ronald  E.

Ronald E.


Job Checkin

System- main Approx Age of System: 9 Refrigerant Type-R410a Metering Device- TXV SP/HP: 113/270 SLT/LLT: 61/89 VSAT/LSAT- 37.2/88.6 Superheat/Subcool- 23/3 Outdoor Entering Air Temp- 68 Outdoor Fan FLA- .90 Compressor RLA/LRA- 11.6 Contactor Voltage- 240/25 Capacitor Rating- 70/ run 7.5 Indoor Return Dry Bulb Temp- 71 Return Wet Bulb Temp- Supply Temp- 54 Temperature Difference- 17 Required Difference- 15-20 Blower FLA- 5.8 Filter Sizes – 20x30x1 16x25x1 Changed Filters – Customer will replace Blew out drain line: Y Notes- performed ac tune up x1, checked indoor unit for proper operations, took amp draws, checked electrical connections. Unit has overflow protection. Did find organic growth on the outside of plenum (see pictures) which can cause the spread throughout the inside or ductwork. Outdoor unit