Jeremy D.

Jeremy D.


Job Checkin

System- Approx Age of System: 1yrs Refrigerant Type- R410a Metering Device- TXV SP/HP: 132/270 SLT/LLT: 59/80 VSAT/LSAT- 45/88 Superheat/Subcool- 13/8 Outdoor Entering Air Temp-75 Outdoor Fan FLA- 1.0 Compressor RLA/LRA-10.6/122 Contactor Voltage-244/26 Capacitor Rating- 43.67/4.89 Indoor Return Dry Bulb Temp-73 Return Wet Bulb Temp-65 Supply Temp- 53 Temperature Difference- 29 Required Difference- 16-29 Blower FLA-4.6 Filter Sizes – 20x25x4 Changed Filters – Y (customer supplied) Blew out drain line: N (No blowout valve) Notes- Unit was operational on arrival. Checked filters. Checked operating pressures and temperatures. Checked indoor and outdoor electrical. Condenser LRA is over rating of 109a. All other components showed no visible issues at this time. Recommend compressor saver-(to re