Job Checkin

System-downstairs rheem Approx Age of System:3 Refrigerant Type- R410a Metering Device- TXV SP/HP:132.9/277.4 SLT/LLT:58.4/76.5 VSAT/LSAT-45.9/90.6 Superheat/Subcool-12.5/14 Outdoor Entering Air Temp-71 Outdoor Fan FLA-.6 Compressor RLA/LRA-8.4 Contactor Voltage-237.7/24.5 Capacitor Rating-46.4 Indoor Return Dry Bulb Temp-71.7 Return wet bulb: 61.9 Supply Temp-53,1 Temperature Difference-18 Required Difference-16-20 Blower FLA-6.5 Filter Sizes –20x25x4 Changed Filters – Y Blew out drain line: Y Notes- System-upstairs Amana Approx Age of System:5 Refrigerant Type- R410a Metering Device- TXV SP/HP:125.8/260.7 SLT/LLT:50.8/80.0 VSAT/LSAT-53.5/85.9 Superheat/Subcool-8.6/5.2 Outdoor Entering Air Temp-71 Outdoor Fan FLA-.8 Compressor RLA/LRA-7.5/ Contactor Voltage-237.8/24.5 Capacitor Rating-35.1/2.9(rated 45/5) Indoor Return Dry Bulb Temp-69.2 Return wet bulb; 60.4 Supply Temp-52.4 Temperature Difference-17 Required Difference-16-20 Blower FLA-5.2 Filter Sizes –