System- Carrier MN: 50TC-A07A2A6A0A0A0 SN: 1617C76075 Approx Age of System: 3 years Refrigerant Type- R410a Metering Device- Fixed SP/HP: 138/376 SLT/LLT: 51/98 VSAT/LSAT- 48/112 Superheat/Subcool-3/14 Outdoor Entering Air Temp-87 Outdoor Fan FLA- 0.76 Compressor RLA/LRA-7.10 Contactor Voltage-475/24 Capacitor Rating-4.83 of 5 Indoor Return Dry Bulb Temp-74 Return Wet Bulb Temp-65 Supply Temp-54 Temperature Difference-20 Required Difference-16 Blower FLA- 2.85 Filter Sizes – 16x16x2 (4) Changed Filters – Yes Belt- AX41- Good condition. Blew out drain line: No Returned tstat to original settings: Yes Unit operational; prior to leaving: Yes Notes- System- Lennox MN: KCA150S4BN1G SN: 5612J01782 Approx Age of System: 8 years Refrigerant Type- R410a Metering Device- TXV Outdoor Fan FLA- 1.38 , 1.42 Compressor 1: 6.63 Compressor 2: 6.58 Contactor Voltage-480/24 Capacitor Rating- 11.35 Indoor Return Dry Bulb Temp-75 Return Wet Bulb Temp-67 Supply