AC Diagnostic System: 1 Refrigerant Type R410A Metering Device-TXV SP/HP 145/315 SLT/LLT 85/101 VSAT/LSAT 51/100. SH/SC 28/4.0 Outdoor Entering Air Temperature 99 Filter Size(s) 20x25x4 Returned tstat to original settings: Y Unit operational; prior to leaving: Y Notes: Upon arrival customer stated that unit has been cooling at all, checked indoor unit, indoor unit was operational, checked outdoor unit unit wasn’t on, checked for proper voltage coming in, wasn’t getting 240, checked breaker, breaker good. Found high pressure reset button had tripped. Reset button and compressor came on but fan didn’t, which caused unit to overheat and shut down. Checked motor, tested continuity on motor. Tried to freely spin blades motor had seized up and not operational, unit is 12yrs old, recommended replacement of condenser due to its age and condition. Home is for sale, and customers are moving out of state soon. Customer requested to replace motor. Recommended OEM motor, availability wa