Job Checkin

System-1 system Approx Age of System: 9 years old Refrigerant Type- R410a Metering Device- TXV SP/HP:110/313 SLT/LLT:66/94 VSAT/LSAT- 36/98 Superheat/Subcool- 30/4.2 Outdoor Entering Air Temp-87 Outdoor Fan FLA- 1.21 Compressor RLA/LRA-13.43/ 132.1. Rated for 117 Contactor Voltage-242 Capacitor Rating-62.3/5.2. Rated 70/7.5 6% Indoor Return Dry Bulb Temp-68 Return Wet Bulb Temp-61 Supply Temp- 56 Temperature Difference-12 Required Difference-16-20 Blower FLA- 3.8 Filter Sizes –20x25x4 Changed Filters – No clean Blew out drain line: No way to blow out drain lines Notes- *system is low on refrigerant customer agreed to charge system, knowing there is a leak somewhere and charging is only a temporary fix. *No safety switches, our blow out valve to clear out drain lines *weak capacitor *p