System-main Approx Age of System:6 Refrigerant Type- R410a Metering Device- TXV SP/HP:117/245 SLT/LLT:71/85 VSAT/LSAT-38/82 Superheat/Subcool-33/0 Outdoor Entering Air Temp-75 Outdoor Fan FLA- 1.1 Compressor RLA/LRA-9.0/62 Contactor Voltage-28/237 Capacitor Rating-35/5 reading 36/5 Indoor Return Dry Bulb Temp-71 Supply Temp- 60 Temperature Difference-11 Required Difference-16-22 Blower FLA-7.2 Filter Sizes –20x25x1 Changed Filters – N (Clean) Blew out drain line: Y Notes-gas flex connector has pipe sealant on the flare fitting and refrigerant was low on charge. Spoke to customer about the refrigerant and issue has been noticed for a while. Issue may be a leak but with no history of refrigerant levels only way to know is by performing a leak test. Us timer would like to add refraining at this time and ke