30045 FM 2978 Rd.
Magnolia, TX 77354
(281) 651-5484

Job Locations
for willis, tx


Map of Willis TX
Ken P.

Ken P.


Job Checkin

System: Main Approx Age of System: 14 Combustible Gas Leak Detection Pipe and fittings leak-free: yes Valves and orifices leak-free: yes Carbon Monoxide Testing Walk-around CO: pass /0 ppm Airside CO: pass /return 0 ppm supply 0 ppm Flue gas CO: pass /52 ppm Ignition and Combustion Delayed ignition: no Flame disturbance: no Flame discoloration: no Motor Amperages and Capacitors Blower motor FLA: 5.00 Induced draft/combustion blower motor FLA: 1.35 Capacitor(s): pass /mfd 19.08 of 20 Temperature Rise Rated: 35-65 Actual: 41 Static Pressures RP 0.34 /FS 0.30 /SP 0.20 TESP: 0.64 Safety Controls Primary limit test: pass Filter sizes: 20x30x1, 14x24x2 Changed filters: no, clean Scheduled next tune up date: June 2, 10-2 arrival time. Notes: Performed heat tune up. Gas flex connector is not properly installed. There is sealant applied to the flare fitting which is a gas leak leak hazard. The system has no overflow protection on the evaporator coil. The UV light needs a re