Conpleted 3 system commercial matience/inspection. Downstairs lobby unit is both heating and cooling at this time. The units capacitor (battery for the compressor and fan) is faulty and needs to be replaced for continuous functioning (raited 40/5 actual 26/4.3 ). Unit is heating properly as well at this time Upstairs left unit is not cooling at this time due to a failed capacitor 40/5. Fan is still operating and circulating air. Unit is heating properly as well at this time. Upstarts right unit is both cooling and heating properly at this time although that capacitor (battery that powers the compressor) is faulty as well (raited 40/5 actual 37/3.5 ) and needs to be replaced to avoid breakdown. Refrigerant pressures on units looked good as far as I could tell (hard to tell with it being 60 degrees outside). All three filters were also changed in lobby areas.