Upon arrival found system not cooling. Checked inside units filter and operation. Found everything operational. Checked outdoor unit and found fan not running and condenser tripping on high head pressure. Found that the bearings in fan motor had gone out. Homeowner approved replacement of condenser fan motor. Replaced 1/4hp 825rpm motor. Installed new cap for motor. Turned system on and checked pressures. Pressures were good. System is now cooling properly at this time. Also homeowner hasn’t had any maintenance for a year. Need to put on schedule.