Found upstairs thermostat blank. Condensate float switch was tripped. Downstairs and upstairs share a common drain line and the downstairs unit sits higher than the upstairs unit causing the downstairs condensate to empty into the upstairs when drain was clogged. The upstairs secondary pan is drained to outside. It is capped and has a float switch installed in it. Prepped upstairs bathroom sink, cut downstairs and upstairs drain line. Installed isolation valves in drain lines. Cleared drain lines with nitrogen. Upstairs blower was left on default and running 3tons of airflow through evaporator coil. Adjusted blower speed on system to low (system is a 2 ton). Reset unit and ran system through cooling cycle. Took temp reading on supply and return air, checked static pressure on duct system (0.82 icw), checked refrigerant charge, and adjusted refrigerant levels (removed a 1.5 lbs of 410a). System is cooling at this time. Quoted customer a float switch for Downstairs on the low end of con