521 J PL 625
Plano , TX 75074
469-252-0599

Job Locations
for frisco, tx


Map of Frisco TX
Jeremy P.

Jeremy P.


Job Checkin

Springtime Air Conditioning Repair for a commercial client near Stonebriar Mall. Upon arrival found system leaking water into back room. Checked RTU and found a clogged drain along with a broken p-trap. System has a negative pressure so drain sucks air instead of pushing air, system cannot drain properly without a p-trap. Found filters completely clogged, found that the evaporator coil needs to be cleaned and blower well needs to be cleaned. Checked pressures and they were fine. System is 22 years old running R-22 refrigerant and recommending replacement soon. With approval fixed drain on package unit and need to return to install 2-16x25x2