Job Checkin

Found condensing unit randomly cutting out. Float switch seemed to be tripping condensing unit out. Checked condensate trap. Condensate trap was at an angle and trap is very shallow not allowing trap to fill with water creating a vapor barrier. Water wouldn't drain out tripping Float switch. Repiped condensate trap and ran system through cooling. Checked drain for proper draining. Unit is draining and drain doesn't seem to be clogged. Unit ran for an hour straight without tripping out or condensing unit cutting off. System cooling at this time.