Angela E.

Angela E.


Job Checkin

Springtime Air Conditioning Repair for a residential customer near Deerfield. Came out today for service call on right side of house r22 2005 unit. Found Dirty 20/20/1 filter. Bad 7.5 run capacitor for blower motor. Insulation levels are low costing more electricity and making units run/work harder. (Disconnect was not fully in pushed in. 240 coming in 50 coming out. [Pushed plug all the way back in.] Now 240 coming in 240 coming to condenser.) Turned on thermostat Checked bearings checked blades checked electrical connections checked contactors checked run capacitors checked Amp draws checked pressures checked filter checked temp split checked duct work checked insulation levels.