521 J PL 625
Plano , TX 75074
469-252-0599

Job Locations
for rowlett, tx


Map of Rowlett TX
Angela E.

Angela E.


Job Checkin

Upon arrival found upstairs condenser disconnect fuse blown. Straight wired condenser and everything came on. Checked amp draw on the compressor and fan motor and they were good. Compressor amps were 10.02/17.2. Checked breaker and found that the breaker wasn’t pushed in all the way slightly, re secured breaker and tightened down wires. Replaced outdoor disconnect with a non fused disconnect. Checked pressures and they were good. Explained to homeowner that if breaker trips breaker may be weak and may need an electrician. System is now cooling properly. System is new and will warranty work.