Upon arrival found upstairs unit not cooling. Checked inside unit and found coil frozen. Checked filter and as soon as I removed filter there was a drastic difference in air flow. Filter was clogged pretty bad. Inserted new customer supplied filter. Line set was frozen as well. Shut down outside unit and left blower running. Will need to return once system has thawed out. Explained to homeowner that if filter was the cause of the issue there will be a service fee. Upon arrival turned condenser on for upstairs and checked pressures, pressures were good and noticed the the compressor for downstairs unit was making a funny sound. Checked pressures and found it low, recommended leak search and homeowner approved. Performed leak search and used my sniffer on the coil. Sniffer detected a leak on the bottom left side of coil. Homeowner approved warranty coil. Office will call to get time set up to replace coil. Homeowner wants to pay for coil and leak search at the same time.