Performed preventative maintenance for a high efficiency Lennox system model #XC17-036-230, serial #5812H03498. Upon arrival I noticed that there was a puddle of water under the system. I shut the system down and removed the evaporator coil access panel. I found the drain pan had a large piece of insulation blocking the drain line. I removed the insulation and tested the drain pan drain line and condensate pump with several cups of hot water to ensure that there were no leaks or clogs. The evaporator coil’s are clean and in good condition. Air filter was replaced in the fall Merv11. Checked all electrical components needed for air conditioning to ensure that they are secure and in good condition. Turned the system on and the blower motor amp draw is at 4.7. The temperature split is at 20. The condenser coil’s are clean and in good condition. The condenser amp draws are 1.3 for the fan and 8.1 for the compressor. The refrigerant pressures are within normal range for the temperature outs