Completed preventative maintenance for heat pump system. System operates on 410A refrigerant. Temp split in HP of 33.5 degrees. Tested electric heat 15kw. Had a heat rise of 51°. Both capacitors in the indoor (rated 370/15mfd)and outdoor (rated 440. 45/5mfd) unit are in good shape. Outdoor contactor is functioning properly. Tested Outdoor fan motor, compressor and blower for proper amperage. Blower operating at 2.5A, outdoor fan motor .6A and compressor at 6.7A. Confirmed proper high and low voltages. Found no damaged or melted wires within the air handler. Filter was replaced recently by customer. System is operating properly at this time. Model #XP14-036-230-03 Serial #5811B18053