Customer called due to boiler system not having any heat this morning when they turned it on. Upon inspection I found that the aquastat relay was going bad and was sticking. This caused the heat call to not fully process which didn’t allow the boiler to heat up. I happen to have the proper aquastat relay on my truck and was able to repair it on the spot. Customer approved repair as well as maintenance when repaired. Installed the new aquastat relay and performed the maintenance on the boiler. Inspected all electrical components. Confirmed proper high and low voltage. confirmed proper 18 psi water pressure. Clean the burners and the burner compartment. Performed combustion analysis on the boiler. System is operating at 83.7% efficiency with a CO level of 14ppm. System is now operating properly and ready for the heating season.