1570 Old York Road
Abington, PA 19001
215-659-4343

Job Locations
for maple glen, pa


Map of Maple Glen PA
Paul T.

Paul T.


Job Checkin

Performed preventative maintenance for a Goodman system model #GMEC801005CN, serial #2012368552. Powered down the system and removed the access panels. Removed and cleaned carbon off of the flame sensor, cleaned out the burners and burner box. Replaced the air filter size 16x25x1. Checked all electrical connections to ensure that they are secure and in good condition. Ensured that the pressure switch is free of any debris. I powered the system back up and called for heat. Took a combustion analysis test and received the following readings, o2 is at 12%, co is at 2ppm. The supply temp is at 128°F. The inducer amp draw is at .33 and the blower amp draw is at 4.9. The system is operating properly at this time. Performed humidifier service. Removed and replaced the old #35 water panel. Cleaned out the housing and drain line. Tested the system for proper operation and leaks. The system is operating properly at this time. Upon arrival the homeowner stated that last night her husband heard