Performed preventative maintenance for a high efficiency carrier system model #59SP5A120E241122, serial #1614A48777. I powered the system down and removed the access panels. I removed and cleaned carbon off of the flame sensor and cleaned out the burners and burner box. Checked the pressure switch for clogs and tested the drain line for leaks and clogs. Replaced two 16x25x4 air filters (homeowner supplied).checked all electrical connections to ensure that they are secure and in good condition. I powered the system back up and called for heat. I took a combustion analysis test and received the following readings, o2 is at 8.9% and the co levels are 5ppm. The inducer motor amp draw is at .23 and the blower motor amp draw is 3.4. The system is operating properly at this time. The homeowner had some concerns about heating the second floor bedrooms. The second floor bedrooms have a separate system located in the basement. This system is set up for ac only , no heat. I explained to the ho