Came out today for a ac system that shut down. Upon arrival the homeowner stated that the system stared right before I arrived. Upon arrival the temperature split was at 15. I connected my gauges and the pressures are 131/326. The superheat is 16 and the subcool is at 9.6. Both coils inside and out are clean and in good condition. The drain pan is clear and the drain line is operating properly. The filter is clean and new. The blower motor amp draw is at 2.6. The condenser amp draws are .50 for the fan and 7.8 for the compressor. I checked all electrical components. They are all secure and in good condition. After the system ran for about 40 minutes the temperature split is now 18. Checked to make sure there is no insulation blocking the blower. Called PA and went over trouble shooting. At this time the system is operating properly. No charge call back.