Job Checkin

Did a preventative maintenance on a high-efficiency gas furnace. During the maintenance I clean the flame sensor washed off the 16 x 25 x 1 filter. Did a combustion test the ppm was 31 and the O2 was 11. Cleaned out the burner box and the blower motor housing. Did an amp check on the inducer motor and blower motor which both me to Furnace specs. Made sure the high-efficiency drain was working properly and cleaned out the trap and also made sure the condensate pump is working. Customer has a water heater from 2009 would recommend replacing it he has a 60 gallon gas water heater there’s only two people living in the house so I would recommend downsizing to a 50 gallon. RGRS-10EZAJS S#Gy5D307PO81201223