Cleaned and checked air conditioner. Checked drain. Checked voltage and amperage draw of motors. Tested capacitors. Found condenser fan run capacitor weak: 11%low. Replaced capacitor and tested amp draw. Checked Freon level. Checked filter. Compressor: 13.35A. Condenser fan: 1.08A . Blower:6.9A .ambient: 80 .liquid line: 93 .suction line: 52.metering device: TXV . Sight glass: clear . Return air: 75.5 .supply air: 74.5. wet bulb: 65 .