John M.

John M.


Job Checkin

Blower run capacitor weak: 10.5%low. Replaced capacitor and tested amp draw. Inducer run capacitor weak: 17%low. Replaced with paralleled capacitors and tested amp draw. Checked temperature rise. 63. High Pressure drop at Purafilter2000: .37”wc. Suggestions: fiberglass or 3M brand filters.