No heat. Found gas valve would not opening! Replaced gas valve. Set gas pressure. 2.6”. Clocked meter: 295k. Inspected heat exchanger & flue venting. Blowdown valve continues to drip when shut off. Recommend replacing blowdown valve. Suggestions: replace blow-down valve.