John F.

John F.


Job Checkin

Today I came to John and Anna’s Temple home to perform a furnace tune up before winter. Upon tune up and inspection of the 24 year old system I tested and adjusted the gas valve, burners, gas pressure and temperature rise. Pulled and cleaned the flame sensor. Tested ignition system, inducing motor and assembly, blower motor and assembly, heat exchanger, humidifier, static pressures, all safety switches and control board. Furnace is in poor condition. The flame sensor, gas valve, control board and safety witches are all working well within manufacturers specifications. The inducing motor has advanced bearing ware and is over amperage. This will fail. The ignition system has approximately 20% life remaining. The furnace has been over heating due to the use of restrictive filters. The temperature rise was 83 with the filter in and is 66 with the filter out. A less restrictive or electronic filter must be used. I have replaced the filter today. The blower motor has over heated at least on