Today I came to Roberts Okotoks home because the furnace stopped working 2 days ago. Upon first inspection I turned up the heat on the thermostat and the system started to run. I tested temperature and found the system running too hot. Because the system is working, we decided to to a furnace tune up. Upon tune up and inspection I tested and adjusted gas valve, burners, gas pressure and temperature rise. Pulled and cleaned the flame sensor. Tested ignition system, inducing motor and assembly, blower motor and assembly, heat exchanger, humidifier, static pressures, all safety switches and control board. Furnace is in fair to poor condition. The gas valve, safety switches, control board, flame sensor and spark igniter are are working well within manufacturers specifications. The inducing / exhaust fan is over amperage and has bearing ware. This indicates impending failure. The blower motor has over heated at least once and has broke its liquified grease pack. This is like a car driving