A/c repair call. The system continues to shut off on low evaporator coil temperature. Check the thermostat sensor and in good condition. Coil temperature range from 55 to 43 degrees. Check setting and operations. System operating normally. Per tech support, move the coil sensor to a different location. Test system and system operating and not icing up and cooling the house properly.