Complete 2 heating maintenance for 17 year old rheem system in Atlanta. Check and find upstairs furnace operating with in manufacturer spec. No concern at this time. Find downstairs furnace operating but overheating and shutting down furnace. Find blower assembly dirty, weak blower capacitor. Find furnace calibration off and need to do combustion calibration. Find Primary pressure sensor sticking. Customer need consultation visit for downstairs system.