Job Checkin

1 system ac inspection complete. Changed filter. Tested mechanical and electrical components. Found system with two returns, one 14” return for downstairs and one 8” return for upstairs. There is no filter at the air handler. There is a 20x20x1 filter in downstairs return grill, there is no filter whatsoever for upstairs return. Filter setup is not correct. Recommend adding filter rack at airhandler so there is actually filtration for both returns. Because of this, evaporator coil is very dirty and clogged which will cause the coil to freeze up and not cool the home, also affects indoor air quality as well. System has no water safety whatsoever and is therefore not up to code. There is no drain pan underneath unit. Drain line is not up to code and likely to clog. Drain line is connected to a small piece of tubing that runs outside. Recommend installing a condensate pump and vinyl tubing for it to have proper drainage and be up to code. Suction line going in to airhandler has secti