Found furnace power switch off. Turned it on and system is operating. Went ahead and checked electrical components for customer. Found blower motor controller running weak out of manufacturer specs, recommend repair. Found water safety not up to code, recommend adding on. Found very rusty evap coil. Found system low on r22, recommend recharging. Found serious pitting on voltage distribution system, recommend repair. Found slight burning on common wire/ terminal going into the voltage absorption system and a weak voltage absorption system. Recommend repair. Installed new blower motor controller. Added on water safety so it is now up to code. Recharged system to 10 degrees superheat. Replaced voltage distribution system. Replaced voltage absorption system and Renovated electrical terminations. Signed customer up for maintanence plan and went ahead and did summer maintenance. Left customer with a replacement filter. Cleared drain line. Chemically washed condenser coil and applied rust pro