Found no issues with heatpump aside from pressures slightly above spec. Noises customer heard were most likely the unit going into defrost mode. Adjusted pressures, to 94.4 on the low side and 335.9 on the high side with an outdoor ambient temperature of 46 degrees. System is heating normal at this time.