Performed 1 A/C system tune, found the system not cooling properly due to high pressures, suction 90, liquid 380, found very dirty condenser coil, after cleaning pressures showed low, recommended to add Freon, the client declined. Changed filter, checked blower and ac components, also checked drain line.