1 system ac pm check complete. Changed filter. Cleared drain line. Changed apco si uv bulb. Tested mechanical and electrical components. Found rusty evaporator coil, this could cause a refrigerant leak in the future. Water safety is code compliant but has no backup, recommend overflow protection switch to serve as a backup to primary water safety switch and to help protect furnace from potential water damage. Found system with worn main electrical switch with electrical pitting present, recommend repair. Found weak capacitor (70/10 uf) recommend repair. Recommend hard start kit to reduce load on compressor so it starts smoother, runs smoother and therefore lasts longer. Recommend surge protection to protect equipment from power surges. System is cooling at this time.