2 furnace pm check complete. Changed filters. Furnace for left side of house: Tested combustion and found low carbon monoxide levels (23 ppm) , slightly high oxygen levels (10.1%) with the furnace operating at 79.6 % efficiency. Furnace has a worn flame safety and a worn ignition system, they are still functioning, but either could fail at any time. Recommend repair. Furnace for right side of house: Tested combustion and found low carbon monoxide levels (30 ppm), slightly high oxygen levels (10.2%) with the furnace operating at 82% efficiency. This system also has a worn ignition system and flame safety system. Recommend repair. Systems are heating at this time.