Sign up 2 Comfort Club memberships. Complete 2 system furnace repair and preventative maintenance check. Change both filter, check operations. Find upstairs Lennox heatpump system lockout on high-pressure safety. Reset system and system operating at this time. Find the Lennox system operating within manufacturer spec. Remove 2 oz of r410 to help with high-pressure lockout. Find the main system operating with a worn/ burnt contactor. Replace contactor for the heatpump system. System operating with the high amp on compressor and fan motor. Compressor operating at 14.5 and fan operating at 1.3 amp. Need to keep a check on fan and compressor. System operating at this time.