Completed diagnostic found unit with clogged drain line and drain line not level to allow water to drain naturally. Cleared line and strapped drain line to be level. Turned system on. System has no back up water safety device. Outdoor system running on r22 refrigerant. Pressures are good with 10 degree subcool. Signed customer up on maintenance plan. Will return to do maintenance.