2 furnace repair and preventative maintenance check complete. Find main system operating normally with manufacturer spec. Find upstairs furnace under-fire and producing high co level at 98ppm on high stage. Complete combustion calibration to help improve temperature, efficiency and reduce Co level 30 ppm. Replace worn flame sensor and replace worn ignition. System operating at this time. Change all filter.