5322 Palmero Ct
Buford, GA 30518
(770) 203-1600

Job Locations
for roswell, ga


Map of Roswell GA
Jon F.

Jon F.


Job Checkin

No cool Roswell. Completed diagnostic. Found system working on arrival. Checked system components. Everything working fine. Coil is clean no leaks detected. Supply plenum is not put together for optimum use. Needs taper plenum to put all ductwork on sides. System missing secondary water safety device to protect furnace from water damage. Gas line is not ran to utilize sediment trap properly. Outdoor unit has good pressures. Recommend adding hard start kit to assist compressor with start up and allow compressor to live longer.