2 furnace preventative maintenance check complete. Changed filters. Dusted out furnace cabinets. Cleared barometric tubing. Upstairs system: I tested the combustion and found safe carbon monoxide levels and good oxygen levels. The system is heating at 80% efficiency, which is what the furnace is rated for. Tested furnace components and found blower motor controller running weak. Recommend repair. I tested the drain line I rebuilt in the summer and it is clear and functional. Main level system: This furnace also has safe carbon monoxide levels, good oxygen levels and is heating at 80% efficiency. The blower wheel is dirty, recommend cleaning. Tested furnace components and found worn ignition system with silica dust build up, it could break/fail at any time. Recommend repair. Aside from that, I found no mechanical issues. Replaced the main level ignition system with moisture resistant ignition system. Replaced upstairs blower motor controller. Systems are heating at this time.