No cool main level Goodman 15 year old air conditioning system in Suwanee. Sign 3 CCI plan and complete 3 heating maintenance. Change 2 16x25x1 filter, check drain and clean 3 condenser coil. Find both heating system operating with weak flame sensor, worn ignition and weak blower capacitor. Find both Evaporator coil In attic leaking and baldy rusted. Both system missing in-line water protection. Find both condenser with low charge and burnt damage capacitor and line wire. Due to system age and conditions, suggest to upgrade equipment. Customer want to repair system for now. Recharge both system with R22, replace main level unit capacitor and repair wires. Replace flame for upstairs system in attic. All 3 system operating at this time.