On arrival system running and cooling producing 20 degrees delta. Drain lines flowed when flushed. Outdoor units contactor is buzzing and in poor condition. Compressor overamping on start up pulling 150 amps when the manufacturers max allowable starting amp draw is 134. Recommended adding a compressor saver to address this and replacing the contactor before it fails. System cooling as I left.