Complete. Goodman HP split. On arrival spoke with homeowner who said heating and cooling are not working. Checked condenser and fan motor is not spinning. Checked dual run cap and reading 0/32.2 rated at 35/5. Replaced cap and tested. Fan motor running and unit heating correctly. Verified heat strips operating as well. System heating correctly on departure.