Complete 1 system Goodman split HP TN said wasn’t cooling properly. I checked the charge and it seemed fine with a 26 degrees SH. The HP had a very week capacitor 40/5 as well as the AH had a 10mfd. Changed both and the HO said she already felt the difference. Delta T was 17 degrees. System working as it should at this time.