Complete: 3 systems worked on All 3 Goodman split HPs. HO said none of the systems were maintaining temp. The Basement system found a bad cap. Changed Cap and system came on checked charge and working great at this time. Main Floor system found system frozen up but not bad so quick de-ice and added 2lbs of r22. System is working great at this time. Top floor system I believe it was struggling bc the both bottom floor units weren’t working. But checked charge and components and all looked good at this time.