Complete: 2 systems worked on DS Unit Heil split HP: Came to replace blower control board. Replaced board and system came on as it should. Then unit cut off. Found condensate line stopped up and condensate pump would no longer pump. Blew out line and replaced condensate pump. Checked charge really hot in the house. Charge looked great. 20degree delta T and 12degree SC. Unit is working great at this time.