41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for carlsbad, ca


Map of Carlsbad CA
Jimmy G.

Jimmy G.


Job Checkin

Arrived on site to Diagnose a no air flow issues on a 2006 condenser and a 1998 Lennox furnace. Condenser located in back yard. Furnace and evaporator coil located in attic. Upon arrival spoke over with client stated few days back noticed system was not cooling home. As well found no air flow being produced in home. He then went out side and found out door unit operating but refrigerant line set were icing up.since has left system off to allow ice to melt. He cycled system in cooling and condenser did turn on but indoor unit was not creating any air flow. Client think it may be a amp fuse and in past it was popped. Inspected indoor and out door unit. Checked electrical wiring, connections, circuit board, and components on both indoor and out door. The summary of findings are as followed. Condenser 1. 2006 condenser. Condenser coil is really dirty. 2. Refrigerant Line set insulation is almost off and exposing line set. 3. Found primary Start control to Be burnt up over years of wear