System was low on refrigerant on arrival. Added 2 lbs to bubble test flare fittings and welds. Found small leak on the suction line flare connection. Tightened the connection and confirmed with soap bubbles. Found no leaks on the welded joints. Charged system by weight up to manufacturing specifications. Tested dealt a T and retested the flare joint.