Jimmy P.

Jimmy P.


Job Checkin

Performed AC Diagnostic on 2005 Lennox system. Upon arrival client stated the outdoor fan motor is no longer spinning and prior to this CAS technician recommended that the fan motors were swapped out due to oil leakage and over amping. During the inspection I found multiple points of concerns that were addressed. 3.5 ton condenser- 1. Duel secondary motor control was dead on hermetic and fan side terminal. This part mostly become defective Due to an over amping component, which would be the compressor and the fan. 2. Both outdoor condensing fan motor have significant oil leakage and are beginning to over amping at this time 3. Power disconnect is not supplied with fuses or surge protection 4. System Contains R22 Which was completely phased out January 1, 2020 Discussed the full condition of the 2005 system. Henry completely understand where it is at right now. Advised that anything done to the system is a Band-Aid and is prolonging the inevitable. Henry does not want to commit into sy